click below
click below
Normal Size Small Size show me how
Water System
| Question | Answer |
|---|---|
| Water well locations | Well #2 at Fire Station 3 (emergency use only) Well #12 13939 Borate (emergency use only) |
| City owns how many acre feet of water | 4036 AF; one AF = 325,850.9 gallons |
| Transmission water main size and location | 16" from FS 2 through MWD connection (Shoemaker and Imperial), to Well #2 at FS3. |
| How many Cubic Feet in an acre foot | 43,560 CF in an AF |
| Gallons per cubic foot | 7.481 gallons |
| MWD connection 1 | South west corner Shoemaker and Imperial, 6" control valve (1200 gpm) and 12" control valve (4800 gpm), reduces pressure from 220 to 80 psi. 15 cubic feet per second or 6733 GPM. |
| MWD connection 2 | Southwest corner Imperial and Carmenita max flow 12.5 CFS (5611 GPM) |
| Total Flow of MWD connections | 27.5 CFS or 12,344 GPM |
| Whittier Connection water system | 6" at Chetle and Rivera, boosts to approximately 60-70 psi. 1800 gpm |
| Emergency connections water system | San Gabriel Valley Water Company @ Dice & Altamar City of Downey at Studebaker & Cecilia City of Cerritos Alondra east of Carmenita (automatic pressure sensing) |
| Size of water reservoirs & pumping capacity | 4 million gallons each, 28 hours pumping at 2300 GPM |
| Booster pumps | 2 at each reservoir with 2300 GPM capacity |
| Booster pump settings | automatically turns on at 45 psi, until static returns to 55 psi. |
| Water main sizes | 12" Industrial 300' spacing, 1200-4800 GPM 6" residential 500-1000' spacing, 600-1800 gpm |
| Fire Flow | 4500 GPM industrial/commercial 10 hours 3500 GPM high density residential 5 hours 2000 GPM SFD 5 hours |
| When was water system formed and acquired? | Formed 1960s and aquired from Suburban Water 1968. |
| Water Master Plans | Original 1966; Master Plan complete 1982, updated 2006 |
| SCADA System Installed | 2003 - Supervisory Control and Data Acquisition. MOnitors flows, water pressure, reservoir levels, power status and some remote operations. |
| How many hydrants in SFS | 1150; 108 miles of mains |
| Pressure Relief Stations (5) | 1. Sorensen and Burke; 2. Near FS 3; 3. Reservoir 2 (Foster Yard); 4. Reservoir 1 (MSY); 5. Greenstone S/O HQ Reservoirs take on water first then dump to storm drains. |
| Elevation northern SFS vs southern SFS | 165' north and 63' south. 102' different. 90' difference between Slauson & Alondra (39 psi) |
| Water Sample Check Points | 20: 12 taken weekly, monthy, quarterly and annual tests for bacteria, carcinogens & contaminants. |
| Water System Pressure (Maximum, minimum non-fire and minimum fire) | 115 psi maximum, 45 psi minimum non-fire flow and 20 psi minimum fire flow |