| Question | Answer |
|---|---|
| AIR FORCE POLICY DIRECTIVE 32-20 | Establishes a fire prevention program at each installation |
| DODI 6055.6 | STAFFING REQUIREMENTS FOR FIRE PREVENTION |
| UFC 3-600-01 | MINIMUM FIRE PROTECTION FOR DOD FACILITIES |
| IBC 20O6 | NEW BUILDING REQUIREMENTS FOR CONSTRUCTION |
| BUILDING FOLDERS NEED TO BE KEPT FOR HOW LONG? | LIFE OF THE BUILDING |
| IF A CONFLICT EXISTS BETWEEN UFC 3-600-01 AND ANY OTHER DOD STANDARD, WHAT TAKE PRECEDENCE? | DOD COMPONATES TECHNICAL GUIDES/ETL'S/ITG, UFC 3-600-01, DOD DOCUMENT, REFERENCE CODE, STANDARD, OR PUBLICATION |
| EGRESS'S FROM ANY BALCONY, MEZZANINE ECT.. SHALL BE NOT LESS THAN HOW MANY? | NOT LESS THAN 2 |
| OCCUPANT LOAD MORE THAN 500 SHALL HAVE HOW MANY EXITS? | NOT LESS THAN 3 |
| OCCUPANT LOAD MORE THAN 1000 SHALL HAVE HOW MANY EXITS? | NOT LESS THAN 4 |
| A SAFE, CONTINUOUS PATH OF TRAVEL FROM ANY POINT IN A STRUCTURE TO A PUBLIC WAY IS WHAT? | MEANS OF EGRESS |
| VARIANCES AND EXEMPTIONS MAY BE GIVEN WHEN IMPOSSIBLE TO COMPLY WITH OSHA & AFOSH GUIDLINES DUE TO OPS NEEDS, MISSION IMPACT, OR TECH REASON. T OR F? | TRUE |
| WHAT ARE THE TWO TYPES OF BUILDING CODES? | PRESCRIPTIVE-BASED, AND PERFORMANCE-BASED |
| CODE/STANDARD THAT STIPULATES IN DETAIL THE TYPES OF MATERIAL CAN BE USED IS WHAT TYPE OF BUILDING CODE? | PRESCRIPTIVE-BASED |
| A ACCEPTABLE LEVEL OF PERFORMANCE THAT MUST MEET WITHOUT SPECIFICALLY STATING HOW ITS ASSEMBLED IS WHAT TYPE OF BUILDING CODE | PERFORMANCE-BASED |
| FOUR MODEL CODES BEFORE ICC WERE? | BOCA, ICBO, IFIC, AND SBCCI |
| SHORT-TERM DEVIATIONS ARE CAUSED BY UNAVOIDABLE CIRCUMSTANCES FOR LESS THEN HOW MANY DAYS? | LESS THAN 90 DAYS |
| TEMPORARY DEVIATIONS ARE SITUATIONS THAT REDUCE CAPABILITY FOR MORE THAN HOW MANY DAY? | 90 DAYS to 1YEAR |
| A REVIEW OF LONG TERM DIVIATIONS MUST BE CONDUCTED EVERY HOW MANY YEARS? | EVERY 3 YEARS |
| DODI 6055.06 | STAFFING REQUIREMENTS FOR MILITARY FIRE DEPARTMENT. |
| IF DISCREPANCIES ARE DISCOVER DURING FUTURE INSPECTIONS, THE BEFORE AND AFTER PHOTOS CAN BE USEFUL TO FIRE INSPECTORS? T OR F? | TRUE |
| MEANS TO CONTROL THE EXPENDITURES OF FUNDS IS WHAT? | A BUDGET |
| TWO GENERAL BUDGETS USED BY FIRE DEPARTMENTS ARE? | CAPITAL AND OPERATING BUDGETS |
| MAJOR PURCHASES THAT COST MORE THAN A CERTAIN SPECIFIED AMOUNT OF MONEY IS WHAT BUDGET? | CAPITAL BUDGET |
| USED TO PAY FOR DAY TO DAY EXPENSES IS WHAT BUDGET? | OPERATING BUDGET |
| THE LARGEST SINGLE ITEM IN THE OPERATING BUDGET OF MOST CAREER FIRE DEPARTMENTS IS WHAT? | COST OF PERSONNEL |
| CAN REPRESENT AS MUCH AS 90% OF AN OPERATING BUDGET? | PERSONAL SERVICES |
| is safety materials, including nominal value incentive adn education items authorized expenditure of funds? T OR F? | TRUE |
| WHAT ARE THE 5 STEPS IN BUDGET PROCESS | PLANNING, PREPERATION, INTERNAL REVIEW, EXTERNAL REVIEW, AND IMPLEMENTATION |
| TWO NATIONAL STANDARDS ARE WHAT? | NFPA AND IBC |
| REQUIRED BY THE AHJ THAT NEW CONSTRUCTION, MODIFICATION OR REHABILITATION CONSTRUCTION DOCUMENTS BE REVIEWED & APPROVED PRIOR TO WHAT? | START OF WORK |
| FAILURE TO COMPLY WITH THE TIME LIMIT OF CORRECTIVE NOTICE ISSUED SHALL BE REGARDED AS A WHAT EACH AND EVERY DAY THAT ITS NOT CORRECTED? | A NEW AND SEPARATE OFFENSE |
| THE TOTAL NUMBER OF PERSONS WHO MAY OCCUPY A BUILDING OR A PORTION OF IT AT ANY ONE TIME IS WHAT? | OCCUPANT LOAD |
| WHEN IS THE OCCUPANT LOAD ESTABLISHED? | DURING THE PLANS AND REVIEW PROCESS |
| WHAT DETERMINES THE OCCUPANT LOAD? | CLASSIFICATION OF USE OF THE BUILDING |
| DOOR ASSEMBLYS IN MEANS OF EGRESS SHALL BE? | SIDE-HINGED OR PIVOTED |
| WIDTH OF THE MEANS OF EGRESS SHALL BE MEASURED AT THE? | NARROWEST POINT OF EGRESS |
| TYPE OF BUILDING CONSTRUCTION WHERE MATERIAL IS NONCOMBUSTIBLE | TYPE I & II |
| TYPE OF BUILDING CONSTRUCTION WHERE EXTERIOR WALLS ARE OF NONCOMBUSTIBLE MATERIAL AND INTERIOR IS OF ANY MATERIAL PERMITTED BY CODE. EXTERIOR WALL 2 HOUR RATING OR LESS | TYPE III |
| HEAVY TIMBER CONSTRUCTION | TYPE IV |
| TYPE OF CONSTRUCTION WHERE EXTERIOR WALLS AND INTERIOR WALLS ARE OF ANY MATERIAL PERMITTED BY IBC | TYPE V |
| CONVERSION OF USE/CHANGE OF OCCUPANCY MUST MEET THE REQUIREMENTS OF CONSTRUCTION WITH IN HOW LONG? | 1 YEAR OR MORE |
| PROVIDES AN ALTERNATIVE APPROACH TO LIFE SAFETY BASED NFPA 101 IS? | NFPA 101A |
| THE QUANTITY OF HEAT WHICH WOULD BE RELEASED BY THE COMBUSTION OF ALL THE COMBUSTIBLE MATERIALS IN A VOLUME, INCLUDING THE FACINGS OF ALL BOUNDING SURFACES | FIRE LOAD |
| HOW MANY CLASSES FOR INTERIOR FINISHES? | 3 CLASSES A, B, C |
| A RESPONSIBLE PERSON OR PERSONS THATS DESIGNATED AND TRAINED TO BE EMERGENCY RESPONSE LIAISON PERSONNEL. | EMERGENCY RESPONSE LIAISON |
| THREE KEY ELEMENTS TO AN EMERGENCY EVACUATION PLAN? | EVACUATION ROUTES, MONITOR DUTIES, & EMPLOYEE/OCCUPANT DUTIES. |
| THE FREQUENCY THAT DRILLS ARE HELD VARIES WITH THE TYPE OF WHAT? | TYPE OF OCCUPANCY AND LOCAL CODE |
| EMPTY PESTICIDE STORAGE CONTAINERS SHALL BE TREATED AS? | FULL CONTAINER |
| PESTICIDES SHALL BE STORED ONLY ON WHAT FLOOR? | FIRST FLOOR |
| OUTSIDE STORAGE SHALL BE GRADED OR SURROUNDED BY A CURB AT LEAST HOW MANY INCHES? | 6 INCHES |
| WHEN DEALING WITH STORAGE OF FLAMMABLES THE THREE TYPES OF SPRINKLER SYSTEMS ARE? | WET PIPE, DELUGE, OR PREACTION |
| AIR INTAKES SHALL BE PROTECTED BY SCREENS NOT LARGER THAN? | 1/2 INCH MESH |
| AIR DUCTS SHALL PASS THROUGH ANY WALL REQUIRED TO HAVE A FIRE RESISTANCE RATING OF? | 1 HOUR |
| DEAD-END STREETS SHALL BE PROVIDED WITH A FIRE APPARATUS TURN AROUND OF HOW MANY FEET? | 150 FEET TURN AROUND |
| PROVIDES A BASIS FOR FUTURE CODE COMPLIIANCE AND ENFORCEMENT | RECORD KEEPING POLICIES |
| WHAT PROVIDES ACCESS TO INFO ESSENTIAL TO THE AF MISSION? | THE AIR FORCE LIBRARY AND INFO SYSTEM (AFLIS) |
| ESTABLISHED TO PROMOTE PUBLIC TRUST BY MAKING INFO AVAILABLE TO THE PUBLIC | DOD FREEDOM OF INFO ACT 5400.7 |
| THE PERMIT SHALL BE ISSUED TO ONE PERSON OR BUISNESS ONLY AND FOR THE LOCATION DESCRIBE. T OR F? | TRUE |
| AHJ SHALL BE PERMITTED TO REQUIRE A REVIEW BY A THIRD PARTY. WHAT IS THIS CALLED? | INDEPENDENT REVIEW |
| BY EXCEPTING THE PERMIT THEY HAVE GIVEN THE AHJ THE PERMISSION TO WHAT?? | INSPECT THEIR WORK |
| 3 STAGES OF PUBLIC FIRE AND LIFE SAFETY EDUCATION ARE? | PLANNING PHASE, DESIGN AND IMPLEMENTATION PHASE, EVALUATION PHASE |
| A. COMPLIANCE WITH MANDATORY AF PROVISION IN AFOSH IS NOT POSSIBLE, B. COMPLIANCE WOULD RESULT IN INCREASED RISK, C. COMPLIANCE WOULD INTERFERE WITH MISSION, D. HAZARD HAS BEEN ASSIGNED A RAC 1,2,3 | VARIANCE REQUESTS |
| The current standard used,to identify the professional levels of performance required for certification of the fire inspector 3level | NFPA 1031 |
| 3 phases of public fire and life safety education | Planning phase, design phase, evaluation phase |
| Issued to one person or business only and for the location or purpose described? | Permit |
| Shall provide evaluation and recommend necessary changes of the proposed design, operation , process , or new technology to the AHJ | Independent Review |
| Present facts and evidence to prove a point, draw a conclusion, or justify a recommendation | Fire Prevention Visit Report 1487 |
| The total capacity of means of egress for any occupied space shall be sufficient for? | The Occupant Load |
| Required means of egress | Occupant load less than 500 = 2, 500-1000= 3, more than 1000= 4 |
| The AHJ shall be permitted to acquire a diagram of for change in? | Increase in occupant load |
| Three means of egress | Exit access, Exit, Exit Discharge |
| Screen doors and storm doors used in means of egress shall have the same requirements as other doors used for egress? T or F | True |
| Plays a important role in life safety during and after emergency situation? | Human psychology |
| The response characteristics are a function of these four characteristics? | Sensibility to physical cues, reactivity, mobility, and susceptibility to products of combustion. |
| Number occupants distribution throughout the building response to the notification, age, health, mental capacity, motivation, and state of wakefulness of the occupants effect what ? | Egress times |
| The physical design of a egress system will also effect? | Egress times |
| Physical factors that will effect egress times? | Width and number of pathways, width tread depth, riser height and number of stairways, change in width of egress paths or the intersection of multiple egress paths. |
| A system, condition, arrangement, material, or equipment submitted for approval to the AHJ and the fire chief as a substitute for a code requirement? | Alternative |
| A option within a code where compliance is achieved by demonstrating through an engineering analysis that a proposed design will meet specified fire safety goals | Performance base design option |
| Pesticide storage shall be separate from food and personal contact items by a? | Liquid tight wall |
| Incomparable material shall not be stored within 25 feet of a pesticide storage areas unless? | Liquid tight wall and separated by a 1 hour wall |
| Fire protection ration for fire doors should be how much percent of the firewall? | 75 percent |
| Fusible links shall have a temp rating of? | 50 percent above max temp |
| Damper testing shall be conducted ever? | 4 years |
| Performed by the installation contractor or owner occupants trained maintenance personnel but not the fire inspector? | Acceptance test |
| If a acceptance test fails the owner is notified how? | In writing within 24 hours |