| Question | Answer |
| Backbone cables are used to provide interconnection between telecommunication rooms, equipment rooms, and entrance facilities. | true |
| The maximum allowable length of a multi-mode fiber optic cable from a main cross-connect to a horizontal cross-connect, is ? or ? . | 2,000 m / 6,560' |
| If Category 3 or 5 backbone cables are intended for high-speed data circuits, their maximum length should not exceed ? or ? . | 90 m / 295' |
| Which is not included in horizontal wiring? | The cables from the ISP into the entrance facility |
| The ANSI/TIA/EIA-568-B.1 standard requires a minimum of at least ? horizontal cable(s) to every work area. | 2 |
| The maximum allowable length for a horizontal cable, regardless of media type, is ? or ? . | 90 m / 295' |
| Twisted pair cross-connect wire or patch cords are used for cross-connecting between horizontal and backbone cable pairs at a telecommunications room. | true |
| Equipment rooms are distinct from telecommunications rooms because of the nature of the ? that they contain. | equipment |
| An entrance facility consists of the entrance of a telecommunications cable from outdoors into a building. | true |
| The entrance facility consists of cables, connecting hardware, protection devices, and other equipment needed to connect cables entering from outdoors to cables that are suitable and approved for use indoors | true |
| The work area consists of the wiring that extends from the telecommunications outlet to the ? . | station equipment |
| Which cable types are recognized for use in the horizontal cabling system? | II. 2-fiber, 62.5/125_m or 50/125_m optical fiber cable III. 4-pair 100 Ω unshielded twisted pair (UTP) cables |
| Which types of cables are recognized for use in the backbone cabling system? | II. 2-fiber, 62.5/125_m or 50/125_m optical fiber cable III. 4-pair 100 Ω unshielded twisted pair (UTP) cables IV. Single-mode optical fiber cable |
| The functions of a telecommunications room may also be performed in an equipment room. | true |
| What is the maximum backbone distance for a UTP data circuit from the MC to HC? | 90 m / 295' |
| does Administration of a cabling system include documentation? | Administration of a cabling system includes documentation (labels, records, drawings, reports, and work orders) of cables, termination hardware, patching and cross-connect facilities, pathways, telecommunications room, and spaces. |
| The TIA/EIA ? Standard defines the requirements for an administration system. | 606 -A |
| TIA/EIA 568-B calls for ? topology for the layout of the system. | star |
| What area includes the cabling that extends from the telecommunications outlet to the workstation? | The work area includes the cabling that extends from the telecommunications outlet to the workstation. |
| The maximum length specified for the work area cabling is ? . | 5 m (16') |
| Structured cabling standards allow for ? equipment room(s) per building. | no limit |
| Open office architecture allows a(n) ? to be implemented for interconnecting permanent horizontal cables to extension cables that are placed in furniture raceways. | consolidation point |
| When implementing centralized fiber architecture, the maximum allowable cable length from a Telecommunications Outlet (TO) to the termination in the Equipment Room (ER) is ? . | 300 m |