| If a strong odor is detected while performing a refrigerant recovery process | A compressor burn out has likely occurred
🗑
|
||||
| Technicians who perform sealed system service on small appliances must have; | Type 1or universal certification
🗑
|
||||
| When a system is in deep vaccum; | Never energize the compressor
🗑
|
||||
| If regulations change after the technician becomes certified; | The technician is responsible for complying with any changes to the regulations
🗑
|
||||
| Recovery equipment must be; | Certified by an epa approved testing lab
🗑
|
||||
| Small appliances in recreational vehicles may use refrigerants such as Ammonia,hydrogen,and water.these refrigerants; | Should not be recovered
🗑
|
||||
| System dependent recovery methods may only be used on appliances containing; | 15 pounds of refrigerant or less
🗑
|
||||
| On a system with an operating compressor,recovery equipment must be capable of recovery | 90% or achieving 4 inches of vacuum
🗑
|
||||
| When pressurizing a system with nitrogen you should; | Both charge through a pressure regulator and install a relief valve in the line downstream from the pressure regulator.
🗑
|
||||
| With a non operating system compressor,recovery equipment must be capable of recovery; | 80 percent of the refrigerant or achieving 4 inches of vaccum
🗑
|
||||
| A small appliance is defined by epa as | Appliances manufactured,charged,and hermetically sealed in a factory that contain 5 lbs of refrigerant
🗑
|
||||
| Type 1 certification is required for; | Persons handling refrigerant during maintenance,service,or repair of small appliances
🗑
|
||||
| Which of the following is an example of a non commendable ? | Air
🗑
|
||||
| Small appliances are equipped with a straight piece of tubing(process stub) that is used; | As the installation location for a piercing-type access valve
🗑
|
||||
| System dependent or passive recovery equipment; | Captures refrigerant into a non pressurized container
🗑
|
||||
| After the refrigerant has been recovered,which of the following can be used to flush the system? | Nitrogen
🗑
|
||||
| Which hc refrigerant is allowed for use in New domestic small appliances? | R-600a
🗑
|
||||
| Recovering multiple types of refrigerants in the same cylinder; | Will make the reclaimed refrigerants unreclaimable
🗑
|
||||
| When using a system-dependent recovery system on an appliance that has an operating compressor,the technician should; | Run the compressor and recover from the high side of the system only
🗑
|
||||
| If after installing a fitting for the purpose of recovering the appliances refrigerant,you find that the system pressure is 0 psig | Refrigerant recovery is not required
🗑
|
||||
| When filling a charging cylinder with a regulated refrigerant; | The refrigerant vapor that is vented off the top of the cylinder must be recovered
🗑
|
||||
| Applying heat,with a heat gun,to the compressor; | Can help vaporize any trapped liquid refrigerant during recovery.
🗑
|
||||
| When using a system -dependent recovery system on an appliance that has a non operating compressor,the technician should; | Place access fitting in both the low and high side of the system
🗑
|
Review the information in the table. When you are ready to quiz yourself you can hide individual columns or the entire table. Then you can click on the empty cells to reveal the answer. Try to recall what will be displayed before clicking the empty cell.
To hide a column, click on the column name.
To hide the entire table, click on the "Hide All" button.
You may also shuffle the rows of the table by clicking on the "Shuffle" button.
Or sort by any of the columns using the down arrow next to any column heading.
If you know all the data on any row, you can temporarily remove it by tapping the trash can to the right of the row.
To hide a column, click on the column name.
To hide the entire table, click on the "Hide All" button.
You may also shuffle the rows of the table by clicking on the "Shuffle" button.
Or sort by any of the columns using the down arrow next to any column heading.
If you know all the data on any row, you can temporarily remove it by tapping the trash can to the right of the row.
Embed Code - If you would like this activity on your web page, copy the script below and paste it into your web page.
Normal Size Small Size show me how
Normal Size Small Size show me how
Created by:
Aaron Q