| IQ Credit | IQ Requirements |
|---|---|
| IQ Prereq #1 | Minimum IAQ Performance ASHRAE 62.1 - 2004 |
| IQ Prereq #2 Environmental Tobacco Smoke Control | Prohibit Smoking; Designated smoking areas 25' from openables and intakes; Continuously exhaust interior areas with 1 Pa neg pressure and 5 Pa avg; measure pressure every 10 sec for 15 min; impermeable deck to deck partitions |
| IQ Prereq #2 Continued | Residential; Seal all penetrations in walls, ceilings and floors ; Weather strip all doors leading into common hallways.; ANSI/ASTM - E779-03 Air Leakage Rate. Calif 2001 energy standards. |
| IQ Credit #1 OA Monitoring | Alarm when OA below 10% design; Monitor CO2 3'6" AFF |
| IQ Credit #2 Increased Ventilation | Increase OA by 30% |
| IQ Credit #3.1 Construction IAQ Plan | SMACNA IAQ Guidelines ; protect on site material from water damage; MERV 8 filters at each return air grille; ASHRAE 52.2 |
| IQ Credit #3.2 IAQ Plan before Occupancy | Building Flush Out 14,000 ft3 per sf maintaining 60 deg 60% RH; or 3500 ft3 OA and ventilate 3 hours per day before occupancy at .3 cfm per sf until 14000 ft3 achieved; Air Quality Testing per EPA. |
| IQ Credit #4.1 Low Emitting Materials, Adhesives & Sealants | SCAQMD Rule 1168; Aerosol Adhesives; GS-36 |
| IQ Credit #4.2 Low Emitting Materials, Paint & Coatings | GS-11; GC-030; SCAQMD Rule 1113 |
| IQ Credit #4.3 Low Emitting Materials, Carpets | Green Label |
| IQ Credit #4.4 Low Emitting Materials , Composite Wood & Agrifiber | No added urea-formaldehyde |
| IQ Credit #5 Indoor Chemical & Pollutant Source Control | 6' rugs at all entrances; Exhaust rooms with fumes; MERV 13 filters; ASHRAE 52.2-1999 |
| IQ Credit #6.1 Controllability of Systems Lighting | provide lighting controls for 90% of occupants. |
| IQ Credit #6.2 Controllability of Systems, Thermal Comfort | HVAC controls for 50% occupants; Operable Windows; ASHRAE 62.1-2204 & ASHRAE 55-2004 |
| IQ Credit #7.1 Thermal Comfort, Design | ASHRAE 55-2004 |
| IQ Credit #7.2 Thermal Comfort, Verification | Thermal survey within 6-18 months; agree to make changes when 20% complain; ASHRAE 55-2004 |
| IQ Credit #8.1 Daylight & Views 75% | Minimum glazing 2% for 75% spaces |
| IQ Credit #8.2 Daylight & Views 90% | Provide windows between 2'6" - 7'6" aff for 90% occupants |